The pneumatic load switch FKN12-12D and the combined device - pneumatic load switch with fuse FKRN12A-12D series are designed for use in three-phase distribution systems of 12 kV and below as control and protection devices for transformers, cables, overhead lines and other power equipment.
Pneumatic load switch FKN12-12D and combined device - pneumatic load switch with fuse FKRN12A-12D series are designed for use in three-phase distribution systems of 12 kV and below as control and protection devices for transformers, cables, overhead lines and other power equipment; Particularly suitable for terminal substations of urban and rural networks, as well as for complete kiosk-type transformer substations. Also suitable for control and protection in ring networks and dual-path redundant power supplies.
FKN12-12D series pneumatic type load switch is capable of switching on and off load current and overload current.
A combined device - a pneumatic type load switch with a fuse of the FKRN12-12D series is capable of switching on and off load current, overload current, and also switching off line short circuit current.
| No. | Parameter name | Unit change | FKN12-12D/630-20 | FKN12-12R.D/125-31.5 | |
| 1 | Rated voltage | kV | 12 | ||
| 2 | Rated frequency | Hz | 50 | ||
| 3 | Rated current | A | 630 | 125 | |
| 4 | Lightning impulse test voltage | kV | Relative to ground and between phases: 75, breaking gap: 85 | ||
| 5 | Power frequency test voltage for 1 min | kV | Relative to ground and between phases: 42, breaking gap: 48 | ||
| 6 | Rated thermal current | kA | 20 (4 s) | ||
| 7 | Rated dynamic current | kA | 50 | ||
| 8 | Rated inrush current (peak) | kA | 50 | ||
| 9 | Rated short circuit breaking current | kA | 20 | 31.5 | |
| 10 | Rated transmission current | kA | 1.5 | ||
| 11 | Maximum breaking current (reference value) | kA | 1.8 | ||
| 12 | Breaking capacity for unloaded transformer | kVA | 1250 | ||
| 13 | Rated charging current of cable | A | 10 | ||
| 14 | Number of active load shedding operations | cycles | >100 | ||
| 15 | Duration of load current disconnection due to shock impact | with | >0.06 | ||
| 16 | Thermal resistance current of the grounding blade | kA | 20(2s) | ||
| 17 | Peak thermal current of grounding blade | kA | 50 | 50 | |
| 18 | Drive motor supply voltage | B | AC/DC220,110 | ||