This series of permanent magnet vacuum load break switches adopts high quality vacuum arcing load chambers and is equipped with the most advanced bistable magnetic drives as the main driving element.
This series of permanent magnet vacuum load break switches adopts high quality vacuum arcing load chambers and is equipped with the most advanced bistable magnetic drives as the main driving element. The drive has a small number of mechanical elements, a modular design of secondary switching control circuits, does not require auxiliary mechanical switches, can be equipped with an intelligent restart protection function, and has low on and off currents. In the on and off state, the control circuit does not require constant voltage, ensuring operation without operating voltage, safety and reliability, as well as significant energy saving effect.
This series of permanent magnet vacuum switches has high switching and switching speeds, its contact opening and additional stroke are 1.5 times higher than those of conventional vacuum contactors. It has excellent breaking characteristics, the short-term withstand current reaches 20 kA. Can be combined with dry-type transformers and disconnectors into a single integrated prepaid commercial metering point with a built-in disconnector, with an optional manual switch-on and switch-off function available. It has a clear advantage in terms of price-quality ratio and is an ideal companion switch for the new generation of prepaid metering points. The insulating body is made by casting epoxy resin, the power frequency withstand voltage is greatly increased to 60 kV and above, and it is also resistant to dust and condensation, making it even more suitable for integrated combined metering stations.
| Parameter name | 12 kV / 160 A | 12 kV / 250 A | 12 kV / 400 A | 12 kV / 630 A |
| Rated voltage of the main circuit, kV | 12 | 12 | 12 | 12 |
| Rated current of the main circuit, A | 160 | 250 | 400 | 630 |
| Rated short-term withstand current, kA | 12.5/16/20 | 12.5/16/20 | 12.5/16/20 | 12.5/16/20 |
| Rated peak current of electrodynamic resistance, kA(kA) | 40 | 40 | 40 | 40 |
| Rated switching current during short circuit, kA | 40 | 40 | 40 | 40 |
| Mechanical wear resistance, 10 thousand cycles | 25 | 25 | 25 | 25 |
| Electrical durability AC3, 10 thousand cycles | 10 | 10 | 10 | 10 |
| Power frequency test voltage (open contact), kV | 42 | 42 | 42 | 42 |
| Test lightning impulse voltage, kV | 75 | 75 | 75 | 75 |
| Industrial frequency test voltage of control circuits, kV | 2 | 2 | 2 | 2 |
| Rated operating frequency, cycles/h | 100 | 100 | 100 | 100 |
| Contact pressure, N | >200 | >200 | >200 | >200 |
| Gap between contacts, mm | 9±1 | 9±1 | 9±1 | 9±1 |
| Contact overtravel, mm | 2±0.5 | 2±0.5 | 2±0.5 | 2±0 |
| Main circuit contact resistance, µOhm | ≤200 | ≤200 | ≤200 | ≤200 |
| Weight, kg | 32 | 32 | 32 | 32 |
| Control voltage, V | AC or DC: 110 / 220 / 380 or customized | |||