This series of high-voltage vacuum contactors is intended for use in AC electrical networks with a frequency of 50–60 Hz with a rated main circuit voltage of 7.2 (12) kV and a rated current of 160 A to 1600 A.
This series of high-voltage vacuum contactors is intended for use in AC electrical networks with a frequency of 50–60 Hz with a rated main circuit voltage of 7.2 (12) kV and a rated current of 160 A to 1600 A. The contactors provide remote switching on and off, and are also designed for frequent starts and control of asynchronous motors, transformers and capacitor banks.
| Parameter | 160.250/12(7.2) | 400/12(7.2) | 630/12(7.2) | 800/12(7.2) | 1250/12(7.2) |
| Rated voltage of the main circuit, kV | 12(7.2) | 12(7.2) | 12(7.2) | 12(7.2) | 12(7.2) |
| Rated current of the main circuit, A | 160,250 | 400 | 630 | 800 | 10,001,250 |
| Switching capacity of the main circuit (switching on), A / 100 cycles | 2500 | 4000 | 6300 | 8000 | 10000 |
| Switching capacity of the main circuit (shutdown), A / 25 cycles | 2000 | 3200 | 5000 | 6000 | 8000 |
| Ultimate breaking capacity, A / 3 cycles | 4000 | 4500 | 6300 | 8000 | 10000 |
| Mechanical wear resistance, 10 thousand cycles | 100 | 100 | 100 | 100 | 100 |
| Mechanical wear resistance of the latch mechanism, 10 thousand cycles | 10 | 10 | 10 | 10 | 10 |
| Electrical durability AC3, 10 thousand cycles | 25 | 25 | 25 | 25 | 25 |
| Wear resistance of the mechanism with permanent magnets, 10 thousand cycles | 20 | 20 | 20 | 20 | 20 |
| Power frequency test voltage of the main circuit (with open contacts), kV | 42(32) | 42(32) | 42(32) | 42(32) | 42(32) |
| Power frequency test voltage (between phases / phase-ground), kV | 42(32) | 42(32) | 42(32) | 42(32) | 42(32) |
| Test lightning impulse voltage, kV | 75(60) | 75(60) | 75(60) | 75(60) | 75(60) |
| Rated operating frequency, cycles/h | 150 | 150 | 150 | 150 | 150 |
| Operating frequency of permanent magnet mechanism, cycles/hour | 30 | 30 | 30 | 30 | 30 |
| Contact pressure, N | >100 | >100 | >100 | >100 | >100 |
| Gap between contacts, mm | 6(5)±0.5 | 6(5)±0.5 | 6(5)±0.6 | 6(5)±0.5 | 6(5)±0.4 |
| Contact overtravel, mm | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 |
| Main circuit resistance, µOhm | ≤200 | ≤200 | ≤200 | ≤150 | ≤150 |