The VS1-12 indoor high-voltage vacuum circuit breaker (also known as ZN63A-12) is designed for use as a complete indoor switchgear in 50 Hz AC power networks with a voltage of 3-10 kV.
The VS1-12 indoor high-voltage vacuum circuit breaker (also known as ZN63A-12) is designed for use as a complete indoor switchgear in 50 Hz AC power networks with a voltage of 3-10 kV. The switch performs protection and control functions for network equipment, as well as for power plants of industrial enterprises and mining operations.
Thanks to its excellent characteristics, this vacuum circuit-breaker is particularly well suited for applications requiring frequent switching at the rated operating current, as well as for repeated breaking of short-circuit currents.
The VS1-12 switch is available in two versions according to the type of drive: with a spring mechanism and with a magnetic mechanism. It can be supplied either in a stationary version or complete with a special withdrawable mechanism for assembly in a withdrawable version.
| No. | Parameter | Unit change | 20 kA | 25 kA | 31.5 kA | 40 kA | |
| 1 | Rated voltage | kV | 12 | ||||
| 2 | Maximum operating voltage | kV | 12 | ||||
| 3 | Rated current | A | 630~1250 | 630~1250 | 630~2000 | 1250~4000 | |
| 4 | Rated short circuit breaking current | kA | 20 | 25 | 31.5 | 40 | |
| 5 | Rated short-circuit inrush current | kA | 50 | 63 | 80 | 100 | |
| 6 | Rated peak current withstand current | kA | 50 | 63 | 80 | 100 | |
| 7 | Rated short-time current (4 s) | kA | 20 | 25 | 31.5 | 100 | |
| 8 | Nominal insulation level | Power frequency test voltage (before and after shutdown) | kV | 42 (48 - open contact) | |||
| Test impulse voltage (before/after breaking) | 75 (84 - open contact) | ||||||
| 9 | Nominal sequence of operations | O-0.3c-CO-180c-CO | |||||
| 10 | Mechanical wear resistance | cycles | 20000 | ||||
| 11 | Number of shutdown operations at rated short-circuit current | cycles | 50 | ||||
| 12 | Rated drive turn-on voltage (DC) | B | AC/DC 110/220 | ||||
| 13 | Rated drive cut-out voltage (DC) | B | AC/DC 110/220 | ||||
| 14 | Gap between contacts | mm | 11±1 | ||||
| 15 | Overtravel (contact spring compression) | mm | 3.5±0.5 | ||||
| 16 | Non-simultaneous switching on/off of three phases | ms | ≤2 | ||||
| 17 | Contact bounce time when turned on | ms | ≤2 | ||||
| 18 | Average shutdown speed | m/s | 0.9~1.2 | ||||
| 19 | Average switching speed | m/s | 0.5~0.8 | ||||
| 20 | Shutdown time | ms | 20~60 | ||||
| 21 | On time | ms | ≤70 | ||||
| 22 | Main circuit resistance per phase (for 630–1250 A) | µOhm | ≤45 | ≤45 | ≤45 | ||
| Main circuit resistance per phase (for 1250–1600 A) | ≤35 | ≤35 | |||||
| Main circuit resistance per phase (for 1600–2500 A) | ≤25 | ||||||
| Main circuit resistance per phase (for 3150–4000 A) | ≤25 | ||||||
| 23 | Permissible total wear thickness of moving/fixed contacts | mm | 30 | ||||